nPro
Navigation

Comparison between nPro and energyPRO

The following validation comparing the two simulation tools energyPRO and nPro was conducted by the engineering company sinnogy GmbH based on a real-life application case. We thank sinnogy for providing the results.

Methodology of the tool comparison

The two software tools differ in the modeling of operational behavior:

  • In energyPRO, the real operational behavior of the generation plants can be modeled in detail (minimum power, start-up and shutdown ramps, minimum operating duration, maximum operating duration).
  • In nPro, the operational behavior is simplified and represented as an ideally modulating generation unit.

To determine the impact of the different modeling approaches on the result of the generated heat, the identical energy system with the same technology parameters was depicted in both, energyPRO and nPro. For this purpose, a heating plant for a heating network is simulated, which includes a combined heat and power plant (CHP), a natural gas boiler, a biomass boiler, and an air-to-water heat pump. The boundary conditions such as energy purchase costs are also identical. The plant configuration includes the following components:

  • Biomass boiler with 500 kWth
  • Combined heat and power plant (CHP) with 236 kWth
  • Air-to-water heat pump with 453 kWth
  • Peak load gas boiler with 1,852 kWth
Setup of the energy system
Figure 1: Setup of the simulated energy system
Table 1: Minimum output, start-up and shutdown ramps, minimum operating duration of generation units in energyPRO
Biomass boilerCHP unitHeat pumpGas boiler
Nominal power500 kW236 kW300 kW1,800 kW
Minimum output300 kW236 kW50 kW600 kW
Start-up rampenabledenabledenabledenabled
Shutdown rampenabledenabledenabledenabled
Minimum operating duration72 h2 h0.5 h0.1 h
Table 2: Minimum output, start-up and shutdown ramps, minimum operating duration, maximum operating duration of generation units in nPro
Biomass boilerCHP unitHeat pumpGas boiler
Nominal power500 kW236 kW300 kW1,800 kW
Minimum outputxxxx
Start-up rampxxxx
Shutdown rampxxxx
Minimum operating durationxxxx

Results of the comparison

The comparison of the heat generation for every technology, the share of the total heat generation, and the deviation of the results from nPro compared to energyPRO is shown in Table 3. The result shows a deviation of less than one percent for all generation technologies. This indicates that the simplified modeling of operational behavior in nPro leads to a very similar result compared to energyPRO. A similar result is found in the scientific study by Wirtz et al. (2021), which examined the impact of depicting detailed operational behavior on the design outcome for mixed-integer optimization models.

Table 3: Heat generation per heat generation unit, share of total heat generation, and deviation of nPro results compared to energyPRO
Heat generation unitenergyPROenergyPROnPronProDeviation
Biomass boiler4,031 MWh55.6 %4,036 MWh55.6 %-0.07 %
Heat pump1,520 MWh21.0 %1,505 MWh20.7 %0.21 %
CHP unit891 MWh12.3 %942 MWh13.0 %-0.70 %
Gas boiler813 MWh11.2 %774 MWh10.7 %0.54 %
Total7,255 MWh100.0 %7,257 MWh100.0 %-0.03 %